Isıtma ve Soğutma Gün Dereceleri

Gösterim Şekli Aylık Değerlendirme Yıllık Değerlendirme


Merkez G/D Oca Şub Mar Nis May Haz Tem Ağu Eyl Eki Kas Ara Yıllık
BOZCAADA

2024
HDD 224 160 153 12 7 556
T≤15 °C 21 22 25 3 2 73
CDD 56 115 96 267
T>22 °C 30 31 31 92
BOZCAADA

2023
HDD 202 240 189 90 16 50 139 926
T≤15 °C 27 25 28 18 4 9 21 132
CDD 11 121 100 38 1 1 272
T>22 °C 9 31 31 22 3 1 97
BOZCAADA

2022
HDD 306 223 319 74 18 4 61 150 1155
T≤15 °C 29 27 29 13 4 1 12 23 138
CDD 8 22 50 87 33 3 203
T>22 °C 4 19 28 31 17 1 100
BOZCAADA

2021
HDD 181 200 256 122 21 96 188 1064
T≤15 °C 20 21 31 21 6 19 22 140
CDD 2 35 102 115 14 268
T>22 °C 1 15 31 31 10 88
BOZCAADA

2020
HDD 289 207 169 134 7 94 141 1041
T≤15 °C 31 26 26 22 2 19 23 149
CDD 6 39 73 88 41 8 255
T>22 °C 6 23 29 31 25 7 121
BOZCAADA

2019
HDD 270 251 159 114 4 14 176 988
T≤15 °C 31 27 24 21 1 4 24 132
CDD 4 59 63 78 15 2 221
T>22 °C 4 28 28 31 17 3 111
BOZCAADA

2018
HDD 257 213 88 22 8 94 271 953
T≤15 °C 30 24 17 6 2 13 30 122
CDD 6 30 115 80 32 263
T>22 °C 4 25 31 31 16 107
BOZCAADA

2017
HDD 388 242 182 98 3 29 108 159 1209
T≤15 °C 31 27 29 19 1 7 21 19 154
CDD 3 45 77 70 38 233
T>22 °C 2 18 29 28 20 97
BOZCAADA

2016
HDD 286 142 158 20 7 39 133 355 1140
T≤15 °C 28 20 23 5 2 8 20 31 137
CDD 4 56 78 69 23 230
T>22 °C 2 25 31 27 18 103
BOZCAADA

2015
HDD 293 265 247 139 31 84 257 1316
T≤15 °C 30 27 31 23 8 20 31 170
CDD 8 51 80 32 0 171
T>22 °C 4 28 31 15 1 79
BOZCAADA

2014
HDD 212 205 189 81 14 4 51 151 196 1103
T≤15 °C 28 27 28 17 4 1 8 24 29 166
CDD 2 24 51 65 10 152
T>22 °C 3 14 27 27 14 85
BOZCAADA

2013
HDD 270 216 165 87 68 87 301 1194
T≤15 °C 29 25 22 16 15 16 30 153
CDD 5 21 33 56 10 125
T>22 °C 5 16 24 31 10 86
BOZCAADA

2012
HDD 369 348 259 45 96 265 1382
T≤15 °C 31 29 31 6 20 28 145
CDD 39 102 78 3 1 223
T>22 °C 25 30 28 7 2 92
BOZCAADA

2011
HDD 299 286 256 180 36 88 241 231 1617
T≤15 °C 31 28 29 27 8 16 30 30 199
CDD 9 82 44 19 154
T>22 °C 10 30 27 18 85
BOZCAADA

2010
HDD 290 185 223 91 6 55 24 180 1054
T≤15 °C 24 23 30 20 2 10 6 19 134
CDD 9 40 71 113 10 243
T>22 °C 6 17 28 31 11 93
BOZCAADA

2009
HDD 250 246 228 131 8 15 122 158 1158
T≤15 °C 29 24 29 25 2 3 23 21 156
CDD 20 87 33 7 0 147
T>22 °C 17 31 28 5 1 82
BOZCAADA

2008
HDD 343 292 124 60 14 20 96 220 1169
T≤15 °C 31 29 24 11 4 5 18 24 146
CDD 0 3 29 59 57 19 167
T>22 °C 1 2 17 31 28 12 91
BOZCAADA

2007
HDD 223 245 203 137 4 16 151 289 1268
T≤15 °C 29 28 29 28 1 3 20 30 168
CDD 0 72 71 69 15 227
T>22 °C 1 19 31 25 9 85
BOZCAADA

2006
HDD 406 299 260 141 61 53 209 290 1719
T≤15 °C 31 28 30 26 11 10 28 31 195
CDD 5 3 56 5 69
T>22 °C 6 6 30 5 47
BOZCAADA

2005
HDD 296 315 247 79 3 61 178 222 1401
T≤15 °C 30 28 28 11 1 11 26 27 162
CDD 0 11 60 65 4 140
T>22 °C 1 12 28 31 6 78
BOZCAADA

2004
HDD 335 263 252 117 3 123 220 1313
T≤15 °C 30 24 30 20 1 16 25 146
CDD 49 40 65 19 3 176
T>22 °C 23 27 27 11 2 90
BOZCAADA

2003
HDD 261 428 366 207 7 37 157 283 1746
T≤15 °C 30 28 31 28 2 7 23 31 180
CDD 11 36 67 15 5 134
T>22 °C 8 29 30 7 4 78
BOZCAADA

2002
HDD 284 142 169 121 22 267 1005
T≤15 °C 31 25 26 23 6 26 137
CDD 26 105 108 25 1 265
T>22 °C 22 31 31 18 3 105
BOZCAADA

2001
HDD 254 225 121 117 30 20 131 313 1211
T≤15 °C 31 27 21 21 8 5 20 29 162
CDD 2 48 38 17 105
T>22 °C 1 26 30 17 74
BOZCAADA

2000
HDD 217 131 229 48 25 46 67 200 963
T≤15 °C 30 22 29 10 5 10 15 28 149
CDD 8 57 21 16 102
T>22 °C 6 24 20 10 60
BOZCAADA

1999
HDD 281 257 211 73 15 62 71 970
T≤15 °C 31 28 28 16 3 12 13 131
CDD 14 49 67 10 7 147
T>22 °C 14 31 29 18 7 99
BOZCAADA

1998
HDD 241 218 260 82 15 11 106 309 1242
T≤15 °C 31 28 31 17 5 3 23 30 168
CDD 10 19 14 43
T>22 °C 12 16 13 41
BOZCAADA

1997
HDD 266 270 319 263 75 8 69 106 198 1574
T≤15 °C 26 28 31 28 16 2 13 21 29 194
CDD 2 35 18 0 1 56
T>22 °C 3 17 16 1 1 38
BOZCAADA

1996
HDD 380 318 373 211 91 193 238 1804
T≤15 °C 31 29 31 29 14 28 29 191
CDD 8 12 60 7 87
T>22 °C 6 12 25 9 52
BOZCAADA

1995
HDD 305 237 243 148 56 86 230 250 1555
T≤15 °C 29 27 30 23 11 17 24 28 189
CDD 4 13 12 4 33
T>22 °C 3 17 12 6 38
BOZCAADA

1994
HDD 243 273 240 94 47 207 310 1414
T≤15 °C 31 28 31 20 11 22 31 174
CDD 8 11 28 71 40 8 166
T>22 °C 5 7 26 31 27 6 102
BOZCAADA

1993
HDD 357 360 281 144 64 15 222 201 1644
T≤15 °C 31 28 29 26 14 3 24 29 184
CDD 0 12 31 28 12 83
T>22 °C 1 8 18 25 10 62
BOZCAADA

1992
HDD 337 336 234 107 41 117 330 1502
T≤15 °C 31 29 27 21 11 18 29 166
CDD 28 41 69 24 25 187
T>22 °C 13 22 28 17 14 94

Kontrolden geçmemiş verilerle hazırlanmıştır.

  1. G/D = Gün-Derece
  2. HDD = Isıtma Gün-Derecesi
  3. CDD = Soğutma Gün-Derecesi
  4. T≤15°C = Sıcaklığın ≤15°C olduğu gun sayısı
  5. T>22°C = Sıcaklığın >22°C olduğu gun sayısı

Gün derece, 24 saatlik periyodun ne kadarının sıcak ve ne kadarının soğuk geçtiğini ölçmeye yarayan bir birimdir.

Isıtma Gün Dereceleri [Heating Degree Days – HDD]

Belirli bir zamanda (gün, ay, yıl) dış ortam ve oda sıcaklığını hesaba katarak soğuğun şiddetini açıklar. Birçok ülke gün derecenin hesabı için farklı tanımlar kullanır. Karşılaştırılabilir ve ortak bir kullanım oluşturmak için Avrupa Topluluğu İstatistik Ofisi (Eurostat) HDD’nin hesabı için aşağıdaki metodu önermektedir.

HDD = (18 °C - Tm) x değer Tm ≤ 15 °C (ısıtma eşiği)
HDD = 0 eğer Tm > 15 °C

Burada; Tm = Günlük ortalama sıcaklık, d= Gün sayısıdır.

Hesaplama günlük bazda yapılır. Aylık ve yıllık gün dereceler bunların toplanması ile bulunur.

ÖRNEK:
Ankara’nın 29 Aralık 2005 günü ortalama sıcaklığı 2.0°C’ dir. Buna göre:
HDD = 18-2=16 dır.

Göreceli ısıtma gün dereceleri ise güncel gün derece ile uzun dönem ortalama gün derece arasındaki orandır. Güncel gün derece / Uzun dönem ortalama gün derece

Soğutma Gün Dereceleri [Cooling Degree Days – CDD]

Belirli bir zamanda (gün, ay, yıl) dış ortam sıcaklığını hesaba katarak sıcaklığın şiddetini açıklar. Resmi olarak belirlenmiş bir eşik sıcaklık olmamakla birlikte inşaat sektörü enerji yönetim pratiklerinde eşik sıcaklık 22°C olarak alınır. Buna göre:

CDD = (Tm - 22) x değer Tm > 22 °C (soğutma eşiği)
CDD = 0 eğer eğer Tm ≤ 22°C

ÖRNEK:Ankara’nın 25 Ağustos 2005 günü ortalama sıcaklığı 25.9°C’ dir. Buna göre:
CDD = 25.9-22 = 3.9 dır.

Gün Derece toplamına neden ihtiyaç vardır?

  1. Isıtma yada soğutma gün dereceleri toplamının bilinmesi binaların ısıtılması yada soğutulması için gerekli olan enerji gereksiniminin bilinmesi açısından önemlidir. Dış ortam sıcaklığı 15°C’nin üzerinde ise ısıtma gereksizdir. Isıtma maliyeti yıllık HDD ile doğrudan orantılıdır. Bunun için 1 yıl içindeki yakıt maliyeti Yıllık HDD’ye bölünerek 1 HDD için ısıtma fiyatı çıkartılır. Daha sonraki hesaplamalar için bu indis kullanılır.
  2. HDD kış mevsiminin sertliğini göreceli olarak önceki ve uzun yıllara göre karşılaştırmak için de kullanılır.
  3. HDD aynı zamanda yeni binalar yapılırken yalıtım, ısıtma ve soğutma giderlerinin hesaplanması için inşaat sektörü tarafından ihtiyaç duyulan bir parametredir.